How do I size a diesel or gas generator set, and what power range does FALAD POWER® manufacture?

To size a generator set, check the running load and the motor-starting condition separately: work out the total load at the moment your largest motor starts in consistent units, and choose a set whose rating and motor-starting capability cover it (VFD, soft-starter or Star-Delta starting lowers the starting demand). Allow a 20–25% reserve margin and account for site altitude (>1,000 m) and ambient temperature (>40 °C) derating per ISO 8528-1; our engineers confirm the calculation for your load list. Shandong Faraday Power Technology Co., Ltd. (FALAD POWER®) manufactures over 1,700 models covering 10–3750 kVA at 50 Hz (1500 rpm, 400/230 V up to 10.5 kV) and 60 Hz (1800 rpm, 208–480 V up to 13.8 kV). Send us your load list or single-line diagram for a free engineering sizing report.

What is the difference between Prime Power, Standby Power and Continuous Power?

ISO 8528-1 defines four ratings:
• Continuous Power (COP): constant load, unlimited running hours — for base-load plants running the same load around the clock.
• Prime Power (PRP): variable load, unlimited annual hours, average load no more than 70% over 24 hours, with 10% overload typically available for 1 hour in every 12 — for mines, construction sites and areas without grid power.
• Limited-Time Running Power (LTP): constant load for up to 500 hours a year, no overload.
• Emergency Standby Power (ESP): variable load during grid outages only, typically up to 200 hours a year, no overload — for hospitals, offices, data centers and factories that need grid backup.
Standby rating is about 10% higher than prime (for example, 500 kVA prime ≈ 550 kVA standby). Every FALAD POWER datasheet lists both prime and standby ratings. Tell us whether the set will be your main power source or a grid backup, and we will quote the right rating. All sets use pure copper brushless alternators from Stamford, Leroy-Somer, Mecc Alte, Marathon, Engga or FALAD POWER.

What are the construction and noise specifications of FALAD POWER silent diesel generator sets?

Designed for hospitals, hotels, data centers, telecom sites and urban construction, our canopies are engineered around four points:
• Noise control: silent and super-silent canopies cut sound pressure to 68–75 dB(A) @ 7 m, using high-density flame-retardant acoustic foam and residential-grade mufflers.
• Corrosion protection: cold-rolled steel panels, sand-blasted and finished with outdoor powder coating against rain and dust.
• Cooling and fuel: radiators rated for 40 °C or 50 °C ambient; an integrated base fuel tank with internal anti-surge baffles for safe transport and refueling.
• Service and handling: lockable access doors, top lifting eyes and forklift pockets for crane or forklift handling.
Tell us your site noise limit and required running time per tank, and we will recommend the right canopy and tank size.

Can I track and control my trailer generators remotely?

Yes. Our rain-proof trailer power stations tow straight to construction sites, mines and emergency sites. With our remote monitoring system you see where every unit is on Google Maps, start or stop it from your phone, and check its running data and movement history — ideal for rental fleets. If a fault occurs, the black box sends the data to our cloud platform and our engineers diagnose it within 2 hours on working days.

What containerized generator sets do you offer, and how many units can run in parallel?

FALAD POWER containerized power stations are built to standard 20GP, 40GP and 40HC container dimensions — 20GP for about 300–700 kVA, 40GP / 40HC for 800–3750 kVA — and CSC-certified containers are available for direct ocean shipping. Choose a walk-in layout with operation, maintenance and duty rooms, or a compact non-walk-in layout. Fuel tank, ventilation, lighting and fire protection are built in. Our paralleling system synchronizes and shares load across up to 32 generator sets, with up to 40 power sources in one system, for island operation, grid-parallel peak shaving and ATS changeover.

Is every generator tested before shipping, and how fast can you deliver?

Yes. Every set passes a factory acceptance test (FAT) on the inductive load bank in our in-house test laboratory, and the test report ships with the unit. In-stock models of some brands can ship in as little as 1 day; standard models usually ship in 7–20 days, and customized or containerized sets in 25–45 days. Warranty terms depend on the engine brand and model and are stated in your quotation, with lifetime technical support.

Which diesel engine brands can you supply, and in what power range?

We build diesel generator sets with 18 engine brands: Weichai (20–3750 kVA), Yuchai (23–3750 kVA), Perkins (10–2500 kVA), SDEC (20–2500 kVA), Baudouin (25–2000 kVA), Cummins (23–2000 kVA), YUXING (20–1250 kVA), HD Hyundai Infracore (63–913 kVA), Volvo Penta (100–750 kVA), Scania (250–750 kVA), DEUTZ (23–750 kVA), FPT (25–563 kVA), Yunnei (23–500 kVA), FAWDE (20–400 kVA), Yangdong (10–94 kVA), Isuzu (25–69 kVA), Kubota (10–50 kVA) and MTU (590–4000 kVA), plus Mitsubishi on request.

Do you supply natural gas, biogas and LPG generator sets?

Yes. We build gas generator sets of 20–1400 kW (25–1750 kVA at 50 Hz, 1500 rpm) with Weichai, Cummins, Yuchai, SDEC and Isuzu gas engines, for natural gas, biogas or LPG. Actual output depends on gas composition and heating value, so we confirm the rating after reviewing your gas analysis.
Biogas requirements (measured within 1 m of the engine gas inlet valve): temperature ≤ 40 °C; pressure 3–20 kPa, changing ≤ 1 kPa/min; CH4 ≥ 55%, changing ≤ 2%/min; H2S ≤ 200 mg/Nm³; NH3 ≤ 200 mg/Nm³; moisture ≤ 40 g/Nm³; particles ≤ 5 μm and ≤ 30 mg/Nm³.
CHP: at rated load, exhaust heat is about 32% of the fuel energy. Our heat-recovery unit turns it into 50–90 °C hot water or saturated steam, raising overall fuel energy utilization by 20–30%.